Defining fire compartments
To define your fire compartments go to the fire compartments tab in the settings menu and click the fire compartments tab.
In this tab the following options are shown:
- Fire comparments defined by - in the dropdown menu:
- Room parameter
- Wall parameter
- Area plan scheme
- Min fire exit width
- Max Compartment size
- Max egress path
To define fire compartments with room parameters:
- Select a room
- Go to properties
- In the properties menu enter a value e.g. "60min" or "firecompartment" in one of the identity data fields (e.g. Image, Comments, Base finish, Ceiling finish, Wall finish, Floor finish).
- Click apply
- Open the Xinaps Fire Safety Assessor
- Select the option "Room parameter" in the "Fire compartments defined by" dropdown menu
- A new dropdown menu will appear. From this dropdown menu select the identity data field in which you have entered your value
- Click OK
Wall parameter
To define fire compartments with wall parameters:
- Select the wall
- Go to properties
- In the comments or mark field enter your value
- Press apply
- Open the Xinaps Fire Safety Assessor
- Open the settings menu by clicking the settings button
- Select the option wall instance parameter from the dropdown menu
- Select mark or comments
- Enter your fire rating value in the search field
- Click OK
Xinaps Fire Safety Assessor will now use walls who contain these terms to create fire compartments and will indicate these with a yellow line in the floorplan under the fire coverage tab.
Defining fire compartments by wall type name:
- Select the wall
- Go to properties
- Change your wall name to e.g. "Wall 200mm - 60min fire rating"
- Click OK or apply
- Open the Xinaps Fire Safety Assessor
- Open the settings menu by clicking the settings button
- Select the option wall instance parameter from the dropdown menu
- Select wall type name
- Enter your search values in the search field
- Click OK
It is possible to indicate requirements to your fire compartment when these are needed. Open the settings menu and under the fire compartments tab fill in the fields of:
- Min fire exit width
- Max Compartment size
The maximum size of your fire compartment - Max egress path
The maximum distance to your emergency egress path
- Calculation steps
- Maximum Egress time
- Flow through (Fire) doors
- Flow through (Fire) stairs
-
Egress Walking speedSpeeds may differ according to stair type and national regulations. Always check the country regulations relevant for your project.
The average walking speed of people when evacuating a building. - Speed over (Fire) stairs
Fire Hose Coverage Settings
The fire Hose Coverage Settings are by default set to Dutch Standards. Different standards may apply in other Countries such as the UK and the USA. Always check the country regulations relevant for your project.
|
Dutch Standard |
United Kingdom Standard |
United States Standard |
Maximum walking distance to fire extinguisher |
20000 (mm) |
|
|
Walking offset around corners |
650 |
|
|
Distance correction factor |
67% |
|
|
Default fire hose length |
20000 |
|
|
Fire hose default water throw length |
5000 |
|
|
The following settings can be adjusted in the settings menu for Fire Hose Coverage:
- Maximum walking distance to fire extinguisher
- Walking offset around corners
- Distance correction factor
- Default fire hose length
- Fire hose default water throw length
- Fire hose name
-
The name of the used fire hose, e.g. Fire-hose, hose, hoses, Fire-hose 20m, brandslanghaspel etc
- Fire extinguisher name
The name of the used fire extinguisher, e.g. Extinguisher, Powder extinguisher, brandblusser etc.Language settings- Exclude room names from the analysis
To set the language in the Fire Safety Assessor, open the settings menu and go to the App settings tab. From the dropdown menu choose:- "Dutch" to change the Xinaps plugins language to Dutch, intendant on Revit
- "Same as Revit" to change the Xinaps plugins to the same language as used in Revit
-
"English" to change the Xinaps plugins language to English, intendant on Revit